MTL4575 – MTL5575 TEMPERATURE CONVERTER THC or RTD input + Alarm
The MTLx575 converts a low-level dc signal from a temperature sensor mounted in a hazardous area into a 4/20mA current for driving a safearea load. Software selectable features include linearisation, ranging, monitoring, testing and tagging for all thermocouple types and 2-, 3- or 4-wire RTDs. (For thermocouple applications the HAZ-CJC plug on terminals 1–3 includes an integral CJC sensor). Configuration is carried out using a personal computer. A single alarm output is provided and may be configured for process alarm or to provide notice of early thermocouple failure.
MTL 5500 Intrinsically Safe Isolators MTL5546Y
MTL5546Y product specification
MTL 5500 Intrinsically Safe Isolators MTL5546Y
SPECIFICATION
See also common specification
MTL 5500 Intrinsically Safe Isolators MTL5546Y
Number of channels
One
Signal source
THC types J, K, T, E, R, S, B or N to BS 60584 and XK
mV input
RTDs 2/3/4-wire platinum to BS 60751
Pt 100, Pt 500, Pt 1000
Cu-50 & Cu-53
Ni 100/500/1000 DIN 43760
MTL 5500 Intrinsically Safe Isolators MTL5546Y
Location of signal source
Zone 0, IIC, T4-6 hazardous area
Division 1, Group A, hazardous location
MTL 5500 Intrinsically Safe Isolators MTL5546Y
Input signal range
–75 to +75mV, or 0 to 400Ω (0 to 1000Ω Pt & Ni sensors)
MTL 5500 Intrinsically Safe Isolators MTL5546Y
Input signal span
3 to 150mV, or 10 to 400Ω (10 to 1000Ω Pt & Ni sensors)
MTL 5500 Intrinsically Safe Isolators MTL5546Y
RTD excitation current
200µA nominal
MTL 5500 Intrinsically Safe Isolators MTL5546Y
Cold junction compensation
Automatic or selectable
Cold junction compensation error
≤ 1.0°C
Common mode rejection
120dB for 240V at 50Hz or 60Hz (500ms response)
Series mode rejection
40dB for 50Hz or 60Hz
Calibration accuracy (at 20°C)(includes hysteresis, non-linearity and repeatability)
Inputs: (500ms response)
mV/THC: ± 15µV or ± 0.05% of input value
(whichever is greater)
RTD: ± 80mΩ
Output: ± 11µA
Temperature drift (typical)
Inputs:
mV/THC: ± 0.003% of input value/°C
RTD: ± 7mΩ/°C
Output: ± 0.6µA/°C
Example of calibration accuracy and temperature drift(RTD input – 500ms response)
Span: 250Ω
Accuracy: ± (0.08/250 + 11/16000) x 100%
= 0.1% of span
Temperature drift: ± (0.007/250 x 16000 + 0.6) µA/°C
= ±1.0µA/°C
Safety drive on sensor failure
Upscale, downscale, or off
Early burnout
Early burnout detection for thermocouples (when selected)
Alarm trips when loop resistance increase is > 50Ω
Output range
4 to 20mA nominal into 600Ω max.
Alarm output (configurable)
Relay ON in alarm, 250mA @ 35V max
Maximum lead resistance (THC)
600Ω
Response time
Configurable – 500 ms default
(Accuracy at 100/200ms – contact MTL)
LED indicator
Green: power and status indication
Yellow: alarm indication, on when contacts are closed
Maximum current consumption (with 20mA signal)
50mA at 24V
Power dissipation within unit (with 20mA signal)
1.2W at 24V
Safety description
Refer to certificate for parameters. Um=253V rms or dc
Configurator
A personal computer running MTL PCS45 software with a
PCL45USB serial interface.
MTL 5500 Intrinsically Safe Isolators MTL5546Y
Other related product models for MTL5546Y as below for your reference.
We mainly supply YOKOGAWA, Siemens, Honeywell , Rosemount, Endress Hauser, ABB, Weidmuller, ABB, MOELLER, Schneider Electic ,Omron ,Fluke ,PEPPERL+FUCHS,etc.
MTL 5500 Intrinsically Safe Isolators MTL5546Y
Why choose us?
1. 100% original product, 100% quality assurance.
If you find a fake. Please contact us without hesitation! We afford the shipment cost! We send you a new product asking zero cent!
2. Varied payment methods.
We adopt T/T, western union and paypal. If you can not trust us , you can choose to pay it via Aliexpress! 100% make your money safe!
3. SHIPPING:
We can shipping all over the world.via DHL,UPS,Fedex,TNT and EMS etc., the packaging is very safe and strong. if you have any special needs,please notify me.
It will take 3 to 7days to reach in your hands.
MTL 5500 Intrinsically Safe Isolators MTL5546Y
Packaging:
Imported with original packaging or standard export packing.Customize design is acceptable.
MTL 5500 Intrinsically Safe Isolators MTL5546Y
Contact
Wuhan Xieyuan Automation Equipment Co., Ltd
Telephone:86-027-85583233
Mobile Phone:86-18671080257
Fax:86-027-85309780
Contact:victor@whxyauto.com
Skype:victordu963@gmail.com
Whatsapp&Viber are available
Address:7-A16,Caishen Commercial Plaza,Hankou Railway Station
MTL 5500 Intrinsically Safe Isolators MTL5546Y